🚚Free Shipping $250+ | Ships in 2-5 Days (U.S.)

Products

BILLDA BLD-YM08S / BLD-YM15S Emergency LED Driver | 8W / 15W | External LiFePO4 Battery | 90-Minute Backup

RESOURCES & DOWNLOADS

(0 Reviews)

Price range: $53.50 through $65.50

Details

Features

The BILLDA YM-S emergency LED driver series offers 8W or 15W emergency output with model-specific DC voltage ranges and 90 minutes of battery backup for compatible LED arrays. Its split design separates the driver from the external LiFePO4 battery pack, giving installers more placement flexibility in narrow fixture spaces.

  • Three model options: BLD-YM08S-300A (8W, 60-300V DC), BLD-YM15S-056A (15W, 25-56V DC), and BLD-YM15S-300A (15W, 60-300V DC).
  • 100-347V AC, 50/60Hz input.
  • 90-minute rated emergency operation with a 24-hour recharge time.
  • External rechargeable LiFePO4 battery; the manufacturer rates the battery for 2000 charge/discharge cycles.
  • Automatic self-testing: 30-second tests every 30 days and 90-minute tests every 360 days.
  • 2-in-1 test switch and charge indicator included for manual testing and status monitoring.
  • UL Listed for factory or field installation; UL 924 and CSA C22.2 No. 141 are listed in the specification.
  • CEC Title 20 / BC compliant, according to the manufacturer.
  • 5-year warranty; battery pro-rated.

Ideal Applications

  • Compatible DC LED arrays within the selected model’s output voltage range
  • Indoor commercial LED fixture emergency backup
  • Fixture designs with limited internal space for a battery pack
  • Compatible OEM and field-installed emergency lighting retrofits

How It Works

During normal operation, the fixture’s normal LED driver powers the LED array while the emergency unit charges its battery. If AC power fails, the emergency driver automatically supplies 8W or 15W of emergency power, depending on the selected model, to the compatible LED array for the rated 90-minute duration. When AC power returns, normal operation and charging resume.

Documents

Download Specifications & Installation Instructions (PDF)

Model Options

  • BLD-YM08S-300A: 8W / 60-300V DC
  • BLD-YM15S-056A: 15W / 25-56V DC
  • BLD-YM15S-300A: 15W / 60-300V DC

Specifications

Brand BILLDA
Model / MPN BLD-YM08S-300A / BLD-YM15S-056A / BLD-YM15S-300A
Product Type Constant-Power Emergency LED Driver
Emergency Output Power 8W / 15W (model dependent)
Output Voltage BLD-YM08S-300A / BLD-YM15S-300A: 60-300V DC; BLD-YM15S-056A: 25-56V DC
Input Voltage 100-347V AC
Input Frequency 50/60Hz
Emergency Runtime 90 minutes
Battery Type Rechargeable LiFePO4
Battery Design Separate external battery pack
Recharge Time 24 hours; more than 24 hours before first use
Maximum Input Current 100mA
Maximum Input Power 8W
Maximum Battery Charging Current 350mA
Operating Temperature 5°C to 60°C (41°F to 140°F)
Self-Test 30-second test every 30 days; 90-minute test every 360 days
Test Switch / Indicator 2-in-1 test switch and charge indicator included
Driver Dimensions (L × W × H) 149 × 44.5 × 25.6 mm (5.87 × 1.75 × 1.01 in)
Driver Mounting Centers 138.3 mm (5.44 in)
Battery Case Dimensions (L × W × H) 8W: 155 × 30.5 × 30 mm; 15W: 164 × 56 × 31 mm
Battery Mounting Centers 8W: 148 mm; 15W: 157.1 mm
Battery Cycle Rating 2000 charge/discharge cycles (per manufacturer)
Installation Location Indoor dry and damp locations
Standards UL 924; CSA C22.2 No. 141
UL File Number E519224
Compliance CEC Title 20 / BC; RoHS and CE marks shown in specification
Warranty 5 years; battery pro-rated

Compatibility & Installation Notes

  • Select the model that matches your LED array: BLD-YM15S-056A supplies 25-56V DC; BLD-YM08S-300A and BLD-YM15S-300A supply 60-300V DC. Confirm that the LED array’s operating voltage stays within the selected range. This is a DC-output backup driver; it is not a 120V AC-output inverter.
  • Follow the supplied diagram for the normal LED driver’s output connections, LED array polarity, battery pack and test accessory connections. Confirm complete fixture and driver compatibility before purchase.
  • Verify the normal LED driver’s power and current against the manufacturer’s 250W / 4A limits. These normal-operation limits are separate from the 8W or 15W emergency output.
  • Requires an unswitched 100-347V AC, 50/60Hz supply. The normal LED driver and emergency unit must use the same branch circuit.
  • For indoor dry and damp locations at 5°C to 60°C (41°F to 140°F). Use a compatible grounded, UL Listed fixture and ground the enclosure.
  • Connect the battery pack only after all other wiring is complete and AC power is on.
  • The battery is external for installation flexibility. The manufacturer states that the sealed battery is not field replaceable; do not attempt battery servicing.
  • Do not use outdoors, in air-handling fixtures, or near gas or electric heaters. Installation and servicing must be performed by qualified personnel; disconnect normal and emergency power before servicing.

Testing & Status Indicators

Solid red indicates charging, solid green indicates a full charge, flashing green indicates self-testing and flashing red indicates an error. The indicator turns off during emergency discharge.

Press the test switch once for a 5-second quick test, hold for 3 seconds to start a 30-second test, or hold for 6 seconds to start a 90-minute test. Hold the switch for one second to end a monthly or annual manual test. Follow the manual’s double-press procedure to suspend emergency output before storage or shipment.

Charging & Storage

Charge for more than 24 hours before first use. During storage, recharge for 24 hours every six months. The manufacturer specifies a maximum storage period of one year and excludes damage caused by prolonged storage without charging from warranty coverage.

Warranty

5-year warranty, with pro-rated battery coverage.